Skip to main content
Engineering LibreTexts

4.6: Unbalanced Faults

  • Page ID
    55580
  • \( \newcommand{\vecs}[1]{\overset { \scriptstyle \rightharpoonup} {\mathbf{#1}} } \) \( \newcommand{\vecd}[1]{\overset{-\!-\!\rightharpoonup}{\vphantom{a}\smash {#1}}} \)\(\newcommand{\id}{\mathrm{id}}\) \( \newcommand{\Span}{\mathrm{span}}\) \( \newcommand{\kernel}{\mathrm{null}\,}\) \( \newcommand{\range}{\mathrm{range}\,}\) \( \newcommand{\RealPart}{\mathrm{Re}}\) \( \newcommand{\ImaginaryPart}{\mathrm{Im}}\) \( \newcommand{\Argument}{\mathrm{Arg}}\) \( \newcommand{\norm}[1]{\| #1 \|}\) \( \newcommand{\inner}[2]{\langle #1, #2 \rangle}\) \( \newcommand{\Span}{\mathrm{span}}\) \(\newcommand{\id}{\mathrm{id}}\) \( \newcommand{\Span}{\mathrm{span}}\) \( \newcommand{\kernel}{\mathrm{null}\,}\) \( \newcommand{\range}{\mathrm{range}\,}\) \( \newcommand{\RealPart}{\mathrm{Re}}\) \( \newcommand{\ImaginaryPart}{\mathrm{Im}}\) \( \newcommand{\Argument}{\mathrm{Arg}}\) \( \newcommand{\norm}[1]{\| #1 \|}\) \( \newcommand{\inner}[2]{\langle #1, #2 \rangle}\) \( \newcommand{\Span}{\mathrm{span}}\)\(\newcommand{\AA}{\unicode[.8,0]{x212B}}\)

    A very common application of symmetrical components is in calculating currents arising from unblanced short circuits. For three-phase systems, the possible unbalanced faults are:

    1. Single line-ground,
    2. Double line-ground,
    3. Line-line.

    These are considered separately.

    Single Line-To-Ground Fault

    The situation is as shown in Figure 10

    The system in this case consists of networks connected to the line on which the fault occurs. The point of fault itself consists of a set of terminals (which we might call “a,b,c”). The fault sets,

    Screen Shot 2021-07-21 at 1.22.07 PM.pngFigure 9: Zero Sequence Network: Wye-Delta Connection, Ungrounded or Delta-Delta
    Screen Shot 2021-07-21 at 1.22.51 PM.pngFigure 10: Schematic Picture Of A Single Line-To-Ground Fault

    at this point on the system:

    \(\ \begin{aligned}
    \underline{V}_{a} &=0 \\
    \underline{I}_{b} &=0 \\
    \underline{I}_{c} &=0
    \end{aligned}\)

    Now: using the inverse of the symmetrical component transformation, we see that:

    \[\ \underline{V}_{1}+\underline{V}_{2}+\underline{V}_{0}=0\label{58} \]

    And using the transformation itself:

    \[\ \underline{I}_{1}=\underline{I}_{2}=\underline{I}_{0}=\frac{1}{3} \underline{I}_{a}\label{59} \]

    Together, these two expressions describe the sequence network connection shown in Figure 11. This connection has all three sequence networks connected in series.

    Double Line-To-Ground Fault

    If the fault involves phases b, c, and ground, the “terminal” relationship at the point of the fault is:

    \(\ \begin{array}{l}
    \underline{V}_{b}=0 \\
    \underline{V}_{c}=0 \\
    \underline{I}_{a}=0
    \end{array}\)

    Then, using the sequence transformation:

    \(\ \underline{V}_{1}=\underline{V}_{2}=\underline{V}_{0}=\frac{1}{3} \underline{V}_{a}\)

    Combining the inverse transformation:

    \(\ \underline{I}_{a}=\underline{I}_{1}+\underline{I}_{2}+\underline{I}_{0}=0\)

    These describe a situation in which all three sequence networks are connected in parallel, as shown in Figure 12.

    Screen Shot 2021-07-21 at 1.26.58 PM.pngFigure 11: Sequence Connection For A Single-Line-To-Ground Fault
    Screen Shot 2021-07-21 at 1.27.58 PM.pngFigure 12: Sequence Connection For A Double-Line-To-Ground Fault

    Line-Line Fault

    If phases b and c are shorted together but not grounded,

    \(\ \begin{aligned}
    \underline{V}_{b} &=\underline{V}_{c} \\
    \underline{I}_{b} &=-\underline{I}_{c} \\
    \underline{I}_{a} &=0
    \end{aligned}\)

    Expressing these in terms of the symmetrical components:

    \(\ \begin{aligned}
    \underline{V}_{1} &=\underline{V}_{2} \\
    &=\frac{1}{3}\left(\underline{a}+\underline{a}^{2}\right) \underline{V}_{b} \\
    \underline{I}_{0} &=\underline{I}_{a}+\underline{I}_{b}+\underline{I}_{c} \\
    &=0 \\
    \underline{I}_{a} &=\underline{I}_{1}+\underline{I}_{2}\\
    &=0
    \end{aligned}\)

    These expressions describe a parallel connection of the positive and negative sequence networks, as shown in Figure 13.

    Screen Shot 2021-07-21 at 1.31.28 PM.pngFigure 13: Sequence Connection For A Line-To-Line Fault

    Example Of Fault Calculations

    In this example, the objective is to determine maximum current through the breaker B due to a fault at the location shown in Figure 14. All three types of unbalanced fault, as well as the balanced fault are to be considered. This is the sort of calculation that has to be done whenever a line is installed or modified, so that protective relaying can be set properly.

    Screen Shot 2021-07-21 at 1.33.14 PM.pngFigure 14: One-Line Diagram For Example Fault

    Parameters of the system are:

    System Base Voltage 138 kV
    System Base Power 100 MVA
    Transformer \(\ T_{1}\) Leakage Reactance .1 per-unit
    Transformer \(\ T_{2}\) Leakage Reactance .1 per-unit
    Line \(\ L_{1}\) Positive And Negative Sequence Reactance j.05 per-unit
    Line \(\ L_{1}\) Zero Sequence Impedance j.1 per-unit
    Line \(\ L_{2}\) Positive And Negative Sequence Reactance j.02 per-unit
    Line \(\ L_{2}\) Zero Sequence Impedance j.1 per-unit

    The fence-like symbols at either end of the figure represent “infinite buses”, or positive sequence voltage sources.

    The first step in this is to find the sequence networks. These are shown in Figure 15. Note that they are exactly like what we would expect to have drawn for equivalent single phase networks. Only the positive sequence network has sources, because the infinite bus supplies only positive sequence voltage. The zero sequence network is open at the right hand side because of the deltawye transformer connection there.

    Screen Shot 2021-07-21 at 1.39.19 PM.pngFigure 15: Sequence Networks

    Symmetrical Fault

    For a symmetrical (three-phase) fault, only the positive sequence network is involved. The fault shorts the network at its position, so that the current is:

    \(\ \underline{i}_{1}=\frac{1}{j .15}=-j 6.67 \text { per }-\text { unit }\)

    Single Line-Ground Fault

    For this situation, the three networks are in series and the situation is as shown in Figure 16

    The current \(\ \underline{i}\) shown in Figure 16 is a total current, and is given by:

    \(\ \underline{i}=\frac{1}{2 \times(j .15 \| j .12)+j .2}=-j 3.0\)

    Screen Shot 2021-07-21 at 1.43.07 PM.pngFigure 16: Completed Network For Single Line-Ground Fault

    Then the sequence currents at the breaker are:

    \(\ \begin{aligned}
    \underline{i}_{1 B} &=\underline{i}_{2 B} \\
    &=\underline{i} \times \frac{j .12}{j .12+j .15} \\
    &=-j 1.33 \\
    \underline{i}_{0 B} &=\underline{i} \\
    &=-j 3.0
    \end{aligned}\)

    The phase currents are re-constructed using:

    \(\ \begin{aligned}
    \underline{i}_{a} &=\underline{i}_{1 B}+\underline{i}_{2 B}+\underline{i}_{0 B} \\
    \underline{i}_{b} &=\underline{a}^{2} \underline{i}_{1 B}+\underline{ai}_{2 B}+\underline{i}_{0 B} \\
    \underline{i}_{c} &=\underline{ai}_{1 B}+\underline{a}^{2} \underline{i}_{2 B}+\underline{i}_{0 B}
    \end{aligned}\)

    These are:

    \(\ \begin{aligned}
    i_{a} &=-j 5.66 & & \text { per-unit } \\
    \underline{i}_{b} &=-j 1.67 & & \text { per-unit } \\
    \underline{i}_{c} &=-j 1.67 & & \text { per-unit }
    \end{aligned}\)

    Double Line-Ground Fault

    For the double line-ground fault, the networks are in parallel, as shown in Figure 17.

    Screen Shot 2021-07-21 at 1.50.30 PM.pngFigure 17: Completed Network For Double Line-Ground Fault

    To start, find the source current \(\ \underline{i}\):

    \(\ \begin{aligned}
    \underline{i} &=\frac{1}{j(.15|| \cdot 12)+j(.15|| .12|| .2)} \\
    &=-j 8.57
    \end{aligned}\)

    Then the sequence currents at the breaker are:

    \(\ \begin{aligned}
    \underline{i}_{1 B} &=\underline{i} \times \frac{j .12}{j .12+j .15} \\
    &=-j 3.81 \\
    \underline{i}_{2 B} &=-\underline{i} \times \frac{j .12 \| j .2}{j .12 \| j .2+j .15} \\
    &=j 2.86 \\
    \underline{i}_{0 B} &=\underline{i} \times \frac{j .12 \| j .15}{j .2+j .12 \| j .15} \\
    &=j 2.14
    \end{aligned}\)

    Reconstructed phase currents are:

    \(\ \begin{aligned}
    \underline{i}_{a} &=j 1.19 \\
    \underline{i}_{b} &=\underline{i}_{0 B}-\frac{1}{2}\left(\underline{i}_{1 B}+\underline{i}_{2 B}\right)-\frac{\sqrt{3}}{2} j\left(\underline{i}_{1 B}-\underline{i}_{2 B}\right) \\
    &=j 2.67-5.87 \\
    \underline{i}_{c} &=\underline{i}_{0 B}-\frac{1}{2}\left(\underline{i}_{1 B}+\underline{i}_{2 B}\right)+\frac{\sqrt{3}}{2} j\left(\underline{i}_{1 B}-\underline{i}_{2 B}\right) \\
    &=j 2.67+5.87 \\
    |\underline{i}_{a} \mid &=1.19 \quad \text { per-unit } \\
    \left|\underline{i}_{b}\right| &=6.43 \quad \text { per-unit } \\
    \left|i_{c}\right| &=6.43 \quad \text { per-unit }
    \end{aligned}\)

    Line-Line Fault

    The situation is even easier here, as shown in Figure 18

    Screen Shot 2021-07-21 at 1.56.08 PM.pngFigure 18: Completed Network For Line-Line Fault

    The source current \(\ \underline{i}\) is:

    \(\ \begin{aligned}
    \underline{i} &=\frac{1}{2 \times j(.15 \| .12)} \\
    &=-j 7.50
    \end{aligned}\)

    and then:

    \(\ \begin{aligned}
    \underline{i}_{1 B} &=-\underline{i}_{2 B} \\
    &=i \frac{j .12}{j .12+j .15} \\
    &=-j 3.33
    \end{aligned}\)

    Phase currents are:

    \(\ \begin{aligned}
    \underline{i}_{a} &=0 \\
    \underline{i}_{b} &=-\frac{1}{2}\left(\underline{i}_{1 B}+\underline{i}_{2 B}\right)-j \frac{\sqrt{3}}{2}\left(\underline{i}_{1 B}-\underline{i}_{2 B}\right) \\
    \left|\underline{i}_{b}\right| &=5.77 \quad \text { per-unit } \\
    \left|i_{c}\right| &=5.77 \quad \text { per-unit }
    \end{aligned}\)

    Conversion To Amperes

    Base current is:

    \(\ I_{B}=\frac{P_{B}}{\sqrt{3} V_{B l-l}}=418.4 A\)

    Then current amplitudes are, in Amperes, RMS:

      Phase A Phase B Phase C
    Three-Phase Fault 2791 2791 2791
    Single Line-Ground, \(\ \phi_{a}\) 2368 699 699
    Double Line-Ground, \(\ \phi_{b}, \phi_{c}\) 498 2690 2690
    Line-Line, \(\ \phi_{b}, \phi_{c}\) 0 2414 2414

    This page titled 4.6: Unbalanced Faults is shared under a CC BY-NC-SA 4.0 license and was authored, remixed, and/or curated by James Kirtley (MIT OpenCourseWare) via source content that was edited to the style and standards of the LibreTexts platform; a detailed edit history is available upon request.